Seaflame Leaflet - page 4

Our Seaflame
TM
Ultra Fire Resistant Cables meet – and exceed – the most rigorous
international testing standards to ensure they can deliver the performance our
customers rely on in challenging environments.
Enhanced performance
for specialist situations
PRYSMIAN SEAFLAME
TM
STANDARDS
IEC 60331-1
EN 50362
IEC 60331-2
EN50200
BS 8491:2008
IEC60331 (1 or 2) +
EN50200mod + BS 8491
TEMPERATURE
830 (+40/-0)°C
830 (+40/-0)°C
1000 (+50/-0)°C
(*)
DURATION
30*, 60, 90, 120 min
30, 60, 120min
from 180 to 360 min
MECHANICAL SHOCK
every 5 min
every 10 min
every 5 min
WATER SPRAY
no
yes, 0.8 l/min
(last 15 min)
no
yes, 0.8 l/min (last 15 min)
WATER JET
no
no
yes, 12.5 l/min
yes, 12.5 l/min
Enhanced flexibility – Seaflame
TM
delivers a 4 x OD bending radius.
*with water spray (Annexe E)
(*) Cu melting point = 1,083°C
Note: All tests carried on same single cable length
What does Seaflame™
mean for our customers?
– A full product range of power, control and instrumentation cables for
shipboard and offshore marine applications with enhanced design
characteristics (minimum bending radius 4 x OD)
– Enhanced fire resistance cables that meet and exceed all existing
related standards (extended time up to 360 mins, increased
temperature up to 1,050°C)
– Cables that withstand the impact of events associated with fire and
fire extinguishing measures (sprinklers spraying, hoses jetting, etc.)
– No need for installation in metallic ducts or protection, leading to
reduced installation materials, time and costs, reduced installation
space and lower weight on board a vessel, and accordingly reduced
total cost of ownership
1,2,3 5,6